Validation
Accuracy and limits
VentiSketch is a concept-stage design tool, so we say plainly how accurate it is, and where you should allow a margin.
What we checked
Before the first release we compared VentiSketch with published wind-tunnel data, full-scale measurements and standard formulas from the ventilation literature.
29wind-tunnel cases checked for the 2D model and ACH
±11%mean difference in flow through the building, per test set
≤2%buoyancy in section against the standard formula
0.923D wind tunnel windward–leeward pressure difference (usual design value ~0.9)
- 2D model and ACH: isolated buildings at several wind angles, building arrays and many opening layouts
- 3D wind tunnel: wind pressure on a standard 6 m cube; windward and roof values fall within the measured range, and results barely change on a finer grid
Limits you should know
- Large openings: with openings over 15% of the wall the flow is underestimated, and the report warns you
- Side walls in the 3D wind tunnel: suction may be about 15–30% low, so ACH for air leaving through side walls may be slightly low (on the safe side)
- Level of result: plan and section results are concept-level estimates for comparing design options, not research-grade CFD or structural wind loading
- Resolution: use at least Medium for numbers; Low is for seeing the flow pattern
Results are not a substitute for engineering analysis, full 3D CFD, on-site measurement or statutory checks (see clause 8 of the licence agreement).